Phase sequence, phase failure, overvoltage, undervoltage unbalanced
Phase sequence, phase failure, overvoltage, undervoltage unbalanced
Phase sequence, phase failure, overvoltage, undervoltage unbalanced
Phase sequence, phase failure, overvoltage, undervoltage unbalanced
Phase sequence, phase failure, overvoltage, undervoltage unbalanced
  • Phase sequence, phase failure, overvoltage, undervoltage unbalanced
  • Phase sequence, phase failure, overvoltage, undervoltage unbalanced
  • Phase sequence, phase failure, overvoltage, undervoltage unbalanced
  • Phase sequence, phase failure, overvoltage, undervoltage unbalanced
  • Phase sequence, phase failure, overvoltage, undervoltage unbalanced

DV2 Voltage Monitoring Relay

Function Features 

-Controls its own supply voltage(True RMS measurement). 

-Set 10-level rated operating voltage through knob. 

– Measuring frequency range:45Hz-65Hz. 

– Voltage measurement accuracy<1%. 

– Relay status is indicated by LED. 

– 1-MODULE,DIN rail mounting.

Description

Technical parametersA208,A220,A230,A240A,A380,A400,A415,A440,A460,A480

N120,N127,N132,N138,N220,N230,N240,N254,N265,N277

FunctionPhase sequence, phase failure, overvoltage, undervoltage and unbalanced voltage of Monitoring 3-phase voltage
Monitoring terminalsL1-L2-L3L1-L2-L3-N
Voltage range

208-220-230-240-380-400-415-440-460-480(P-P)

120-127-132-138-220-230-240-254-265-277(P-N)

Rated supply frequency45Hz-65Hz
Measuring range150V-600V85V-345V
Threshold adjustment voltage2%-20%of Unselected
Adjustment of asymmetry threshold5%-15%
Hysteresis2%
Phase failure value70% of Un selected
Time delayAdjustable 0.1s-10s,10%
Measurement error≤1%
Run up delay at power-up0.5s time delay
Konb setting accuracy10% of the scale value
Reset time1000ms
OutputSPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Temperature coefficient0.05%/℃,at=20℃(0.05%℉,at=68℉)
Mechanical life1×10^7
Electrical life(AC1)1×10^5
Operating temperature
-20℃ to +55℃(-4℉ to 131℉)
Storage temperature-35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage categoryIII
Pollution degree2
Max.cable size(mm 2)solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
Tightening torque0.5Nm
Dimensions87×45×77.5mm
Weight  130g-135g
StandardsEN61812-1,IEC60947-5-1
send inquiry to us

Related Product

Chat with us