Function Features 

-Controls its own supply voltage(True RMS measurement). 

-Set 10-level rated operating voltage through knob. 

– Measuring frequency range:45Hz-65Hz. 

– Voltage measurement accuracy<1%. 

– Relay status is indicated by LED. 

– 1-MODULE,DIN rail mounting.

Description

Technical parameters

M480

M277

FunctionPhase sequence, phase failure, overvoltage, undervoltage and unbalanced voltage of Monitoring 3-phase voltage
Monitoring terminalsL1-L2-L3L1-L2-L3-N
Voltage range

208-220-230-240-380-400-415-440-460-480(P-P)

120-127-132-138-220-230-240-254-265-277(P-N)

Rated supply frequency45Hz-65Hz
Measuring range150V-600V85V-345V
Threshold adjustment voltage2%-20%of Unselected
Adjustment of asymmetry threshold5%-15%
Hysteresis2%
Phase failure value70% of Un selected
Time delayAdjustable 0.1s-10s,10%
Measurement error≤1%
Run up delay at power-up0.5s time delay
Konb setting accuracy10% of the scale value
Reset time1000ms
OutputSPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Temperature coefficient0.05%/℃,at=20℃(0.05%℉,at=68℉)
Mechanical life1×10^7
Electrical life(AC1)1×10^5
Operating temperature
-20℃ to +55℃(-4℉ to 131℉)
Storage temperature-35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage categoryIII
Pollution degree2
Max.cable size(mm 2)solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
Tightening torque0.5Nm
Dimensions90×36×70mm
Weight  61g-66g
StandardsEN61812-1,IEC60947-5-1